Earthing system

In electricity supply systems, an earthing system defines the electrical potential of the conductors relative to the Earth's conductive surface. The choice of earthing system can affect the safety and electromagnetic compatibility of the power supply, and regulations can vary considerably among countries. Most electrical systems connect one supply conductor to earth (ground). If a fault within an electrical device connects a "hot" (unearthed) supply conductor to an exposed conductive surface, anyone touching it while electrically connected to the earth (e.g., by standing on it, or touching an earthed sink) will complete a circuit back to the earthed supply conductor and receive an electric shock.

A protective earth, known as an equipment grounding conductor in the US National Electrical Code, avoids this hazard by keeping the exposed conductive surfaces of a device at earth potential. To avoid possible voltage drop no current is allowed to flow in this conductor under normal circumstances, but fault currents will usually trip or blow the fuse or circuit breaker protecting the circuit. A high impedance line-to-ground fault insufficient to trip the overcurrent protection may still trip a residual-current device (ground fault circuit interrupter or GFCI in North America) if one is present.

In contrast, a functional earth connection serves a purpose other than shock protection, and may normally carry current. Examples of devices that use functional earth connections include surge suppressors and electromagnetic interference filters, certain antennas and measurement instruments. But the most important example of a functional earth is the neutral in an electrical supply system. It is a current-carrying conductor connected to earth, often but not always at only one point to avoid earth currents. The NEC calls it a groundED supply conductor to distinguish it from the equipment groundING conductor.

Until the mid 1900s, power outlets generally lacked protective earth terminals. Devices needing an earth connection often used the supply neutral. Some used dedicated ground rods. Many appliances had polarized plugs to maintain a distinction between "live" and "neutral", but using the supply neutral for equipment earthing was highly problematical. "Live" and "neutral" might be accidentally reversed in the outlet or plug, or the neutral-to-earth connection might fail or be improperly installed. Even normal load currents in the neutral might generate hazardous voltage drops. For these reasons, most countries mandated dedicated protective earth connections that are now almost universal.

Contents

IEC terminology

International standard IEC 60364 distinguishes three families of earthing arrangements, using the two-letter codes TN, TT, and IT.

The first letter indicates the connection between earth and the power-supply equipment (generator or transformer):

T
Direct connection of a point with earth (Latin: terra);
I
No point is connected with earth (isolation), except perhaps via a high impedance.

The second letter indicates the connection between earth and the electrical device being supplied:

T
Direct connection of a point with earth
N
Direct connection to neutral at the origin of installation, which is connected to the earth

TN networks

In a TN earthing system, one of the points in the generator or transformer is connected with earth, usually the star point in a three-phase system. The body of the electrical device is connected with earth via this earth connection at the transformer.

The conductor that connects the exposed metallic parts of the consumer is called protective earth (PE). The conductor that connects to the star point in a three-phase system, or that carries the return current in a single-phase system, is called neutral (N). Three variants of TN systems are distinguished:

TN−S
PE and N are separate conductors that are connected together only near the power source. This arrangement is the current standard for most residential and industrial electric systems in North America and Europe.
TN−C
A combined PEN conductor fulfills the functions of both a PE and an N conductor. Rarely used.
TN−C−S
Part of the system uses a combined PEN conductor, which is at some point split up into separate PE and N lines. The combined PEN conductor typically occurs between the substation and the entry point into the building, and separated in the service head. In the UK, this system is also known as protective multiple earthing (PME), because of the practice of connecting the combined neutral-and-earth conductor to real earth at many locations, to reduce the risk of broken neutrals - with a similar system in Australia being designated as multiple earthed neutral (MEN).
TN-S: separate protective earth (PE) and neutral (N) conductors from transformer to consuming device, which are not connected together at any point after the building distribution point. TN-C: combined PE and N conductor all the way from the transformer to the consuming device. TN-C-S earthing system: combined PEN conductor from transformer to building distribution point, but separate PE and N conductors in fixed indoor wiring and flexible power cords.

It is possible to have both TN-S and TN-C-S supplies from the same transformer. For example, the sheaths on some underground cables corrode and stop providing good earth connections, and so homes where "bad earths" are found get converted to TN-C-S.

TT network

In a TT earthing system, the protective earth connection of the consumer is provided by a local connection to earth, independent of any earth connection at the generator.

The big advantage of the TT earthing system is the fact that it is clear of high and low frequency noises that come through the neutral wire from various electrical equipment connected to it. This is why TT has always been preferable for special applications like telecommunication sites that benefit from the interference-free earthing. Also, TT does not have the risk of a broken neutral.

In locations where power is distributed overhead and TT is used, installation earth conductors are not at risk should any overhead distribution conductor be fractured by, say, a fallen tree or branch.

In pre-RCD era, the TT earthing system was unattractive for general use because of its worse capability of accepting high currents in case of a live-to-PE short circuit (in comparison with TN systems). But as residual current devices mitigate this disadvantage, the TT earthing system becomes attractive for premises where all AC power circuits are RCD-protected.

The TT earthing system is used throughout Japan, with RCD units in most industrial settings. This can impose added requirements on variable frequency drives and switched-mode power supplies which often have substantial filters passing high frequency noise to the ground conductor.

IT network

In an IT network, the distribution system has no connection to earth at all, or it has only a high impedance connection. In such systems, an insulation monitoring device is used to monitor the impedance.

Other terminologies

While the national wiring regulations for buildings of many countries follow the IEC 60364 terminology, in North America (United States and Canada), the term "equipment grounding conductor" refers to equipment grounds and ground wires on branch circuits, and "grounding electrode conductor" is used for conductors bonding an earth ground rod (or similar) to a service panel. "Grounded conductor" is the system "neutral". Australian standards use a modified PME earthing system called Multiple Earthed Neutral (MEN). The neutral is grounded(earthed) at each consumer service point thereby effectively bringing the netral pd to zero along the whole length of LV lines.

Properties

Cost

Fault path impedance

If the fault path between accidentally energized objects and the supply connection has low impedance, the fault current will be so large that the circuit overcurrent protection device (fuse or circuit breaker) will open to clear the ground fault. Where the earthing system does not provide a low-impedance metallic conductor between equipment enclosures and supply return (such as in a TT separately earthed system), fault currents are smaller, and will not necessarily operate the overcurrent protection device. In such case a residual current detector is installed to detect the current leaking to ground and interrupt the circuit.

Safety

Electromagnetic compatibility

Regulations

Application examples

Comparison of Earthing systems

TT IT TNS TNC TNCS MEN
Earth fault loop impedance High Highest Low Low Low Low
RCD preferred? Yes No Yes No No After N and PE separates
Need earth electrode at site? Yes Yes No No No No
PE conductor cost Low Low Highest Least High Least Cost. Earth conductor size is 6mm^2
Risk of broken neutral No No No Highest High No
Safety Safe Less Safe Safest Least Safe Safe Integrity of earth at customer installation needs periodic checking.
Electromagnetic interference Least Least Low High Low Low
Safety risks High loop impedance Double fault, overvoltage Broken PE Broken neutral Broken neutral Can result in electrocution if earth is broken polarity is reversed.
Advantages Safe and reliable Continuity of operation, cost Safest Cost Safety and cost Inexpensive. It is effective in keeping neutral pd at zero potention along the line.